174
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Commissioning procedure
Controls
Record the following final control variables.
• Controller type
• Controller address
• Boot version
• Bios version
• Display address
• Display type
• Strategy reference
• Room setpoint
• Room limits (Temperature/ Humidity – High/ low)
• Proportional band
• Dead band
• Compressor off time
IMPORTAN
T
Ensure that the controls are reset back to auto. Acknowledge this on the commissioning
sheet.
Commissioning