Installation, Maintenance and Commissioning Manual :6877419 02/2013
Commissioning procedure
Controls
Record the following final control variables.
Controller type
Controller address
Boot version
Bios version
Display address
Display type
Strategy reference
Room setpoint
Room limits (Temperature/ Humidity – High/ low)
Proportional band
Dead band
Compressor off time
IMPORTAN
T
Ensure that the controls are reset back to auto. Acknowledge this on the commissioning
sheet.
Commissioning