EasyManua.ls Logo

AIREDALE SmartCool D - Alarm Code Directory - EEV Related

Default Icon
218 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
185
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Code
Description
Auto Reset
Unit
Disabled
Component
Disabled
Cause Action
AL038
Low Return Air
Temperature
AL039
High Supply Air
Temperature
AL040
Low Supply Air
Temperature
AL041
Circuit 1 High
Pressure
Indicates that circuit 1 has
been exposed to high pressure.
Circuit 1 will be shut down,
Once the pressure within circuit 1 has
decreased to a safe level the alarm can be
manually reset
AL042
Circuit 2 High
Pressure
Indicates that circuit 2 has
been exposed to high pressure.
Circuit 2 will be shut down.
Once the pressure within circuit 2 has
decreased to a safe level the alarm can be
manually reset
AL043
EEV Driver 1
Motor Error
Indicates an motor error within
EEV driver 1. During this alarm
circuit 1 is switched off.
This alarm can be manually reset once the
problem with the EEV is resolved
Troubleshooting