Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data –X2C0
SC19D033-X2C0-0 SC19D038-X2C0-0 SC19D045-X2C0-0
Standard Condenser Match 1 x CR50 1 x CR65 1 x CR65
Unit Data Full function - X2C0
Nominal Run Amps A 51.7 54.5 56.4
Maximum Start Amps A 113.2 130.2 143.2
Recommended Mains Fuse Size A 63 63 63
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50Hz
Control circuit VAC 24 24 24
Unit Data Cooling only –X2C0
Nominal Run Amps A 29.8 35.6 39.4
Maximum Start Amps A 91.3 111.2 126.1
Recommended Mains Fuse Size A 40 40 50
Evaporator Fan Motor - Per Fan
Motor Type EC EC EC
Quantity x Motor Size kW 2 x 2.2 2 x 2.2 2 x 2.2
Full Load Amps A 3.3 3.3 3.3
Locked Rotor Amps A 3.3 3.3 3.3
Compressor 1 , Circuit 1
Motor Size kW 4.6 5.6 6.3
Nominal Run Amps A 8.5 11.4 13.3
Locked Rotor Amps A 70 87 100
Type of Start Direct On Line
Compressor 2, Circuit 1
Motor Size kW 4.6 5.6 6.3
Nominal Run Amps A 8.5 11.39 13.27
Locked Rotor Amps A 70 87 100
Type of Start Direct On Line
Standard Condenser Match - AC Motor Per Fan
Quantity x Motor Size kW 2x 0.6 2 x 0.6 2 x 0.6
Full Load Amps A 2.62 2.62 2.62
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating (Total) kW 21 21 21
Current Per Phase A 30.31 30.31 30.31
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
Full Load Amps A 8.67 8.67 8.67
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size kW 2 x 3.1 2 x 3.1 2 x 3.1
Full Load Amps A 4.8 4.8 4.8
Locked Rotor Amps A 4.8 4.8 4.8
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size kW 2 x 0.73 2 x 0.73 2 x 0.73
Full Load Amps A 3.3 3.3 3.3
Condenser Match - SCAF Fan
Quantity x Motor Size kW 2 x 1.4 2 x 1.4 2 x 1.4
Full Load Amps A 6 6 6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X2C0