AS-D+—AS-P Series Instruction Manual 23
AirSep Corporation
The ‘Local Message Display’ icon displays the different status of the generator
namely Stopped, Running, Standby, and Alarm. This display will also show the
recent alarms if you push and hold.
This window will populate with the most recent, highest priority message of the
system. The priorities are listed here, from highest to lowest:
Priority List
1. Runtime Power Loss
2. Emergency Stop
3. Stopped
4. Shutdown: High Bed Pressure
5. Shutdown: Low Instrument Air
6. Shutdown: Low Oxygen
7. Standby
8. Stop Sequence Activated
9. Alarm: High Bed Pressure
10. Alarm: Low Oxygen Concentration
11. Running
The icons ‘Oxygen Generator’ and ‘Output Parameters’ take the user to dedicated
screens described later in this section. Lastly, by touching ‘Screen Cleaning’ icon
at the bottom right corner of the information display, a blank screen for cleaning
purposes is displayed and the ‘Maintenance’ icon will display a screen that provides
guidelines for the general maintenance of the unit. The ‘Silence Horn’ icon bypasses
the horn for 10 minutes during an alarm or shutdown condition.