System Parameters and Default Values
Free cooling humidity limit
Maximum humidity for free cooling
Humidity below the limit at which free cooling will
be re-enabled
Enable Partial Free Cooling
Min. temp. diff. for
freecool
Damper will open if the indoor-outdoor
temperature difference is larger than this value
Damper will close if the indoor-outdoor
temperature difference is smaller than this value
Minimum damper opening percentage
Enable free cooling only at high indoor
temperatures
Emergency ventilation
enable
Enable emergency ventilation
Temperature above setpoint at which emergency
ventilation will activate
Temperature below emergency ventilation
setpoint at which emergency ventilation will
deactivate
Force compressor to stop during free cooling
Table 5-14 Parameters in the Sensors Menu
Note: Parameters in gray can only be accessed by connecting a PGD to the unit or via the html interface.
Minimum allowed humidity
value
Maximum allowed humidity
value
Sensor Settings (Unit
Only)
Minimum allowed high pressure
sensor value
Maximum allowed high
pressure sensor value
Minimum allowed low pressure
sensor value
Maximum allowed low pressure
sensor value
Outdoor temperature sensor
offset
Room temperature sensor
offset
Outdoor humidity sensor offset
Supply temperature offset