12.6.2.3TotalProtectionLevelDenition
The total protection level is dened by the higher level of protection received.
12.6.3 Deicing
12.6.3.1 Deicing Starting Conditions
12.6.4.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT is 8 degree lower then the ambiant temp and the minimum time from the last deicer is passed.
Case 2: OCT is 12 degree lower then the ambiant temp and 30 minutes from the last deicer wa passed.
Deicing interval time when compressor is rst started in heat mode, is 10 minutes if OCT < -2, and is 40 minutes
in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time.
In case one of the thermistors is bad the deicer will initiate in predened intervals.
Deicer may accure also when the unit switch to stanby and the OCT is 8 degree lower then ambiant
temperature
12.6.3.2 Deicing Protection Procedure