TROUBLE SHOOTING
HKD DCI 57 Version - 2
11.2.8 Over voltage or too low voltage protection diagnosis and solution (P1)
Error Code
P1
Malfunction decision
conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Supposed causes
Power supply problems.
System leakage or block
PCB faulty
Check if the power supply is
normal.
Check if all the connections
and wires are good?
Disconnect the unit with power
supply and try to restart the unit
when power supply gets normal.
No
Yes
No
Correct the connections or replace
the wires.
Yes
Power on and when the unit is in
standby, check if the voltage
between P and N is around DC
310V or 340V or 380V? Then start
up the unit, measure the voltage
between P and N. Is it in
220V~400V?
Replace outdoor mainl PCB.
Yes
No
Replace the IPM board if it is separate
with main PCB.