Error 5: Temperature probe - Open circuit
The zone ceases to measure the room temperature, therefore the zone cannot generate demand. Proceed to replace it of the
device or sent it for repair.
Error 6: Temperature probe - Short circuit
The zone ceases to measure the room temperature, therefore the zone cannot generate demand. Proceed to replace it of the
device or sent it for repair.
Error 8: Wired Lite thermostat not found
The zone ceases to measure the room temperature of an associated wired Lite thermostat, therefore the zone cannot generate
demand. Check in your Blueface tharmostat which Lite thermostat is not working properly. To solve this incident check:
1. Connection: Check the polarity of the main control board and thermostat connectors.
2. Wiring: Check that the voltage between the poles (A/ -) and (B/ -) is correct (1.8 VDC for Supermaster)
3. Verify the thermostat microswitch corresponds with the zone associated. If not, activate it using the tab with the value
needed.
Remember: If you need to change the zone number, reset the thermostat and start association process.