Unit present in unassigned slot
...................................................................................................................................................................................................................................
Alarm identifier
UPUS
Information A unit is detected in a slot which has not been provisioned.
Alarm category Equipment
ASAP equipment
Alarm severity
(default setting)
Information
Reporting state
(default setting)
Reported
Local indications The red fault LED on the unit is lit.
Cause A unit is installed but it has not (yet) been provisioned.
Actions Have the unit provisioned, or
remove it from the indicated slot.
Note(s) An empty slot, not configured, will not generate an alarm message.
Alarm messages
...................................................................................................................................................................................................................................
1-210
Alcatel-Lucent - Proprietary
See notice on first page
365-312-803R7.2
Issue 4, May 2007