AM/AMS units (AC powered)
...................................................................................................................................................................................................................................
Horizontal rack mounting
The horizontal rack mounting is allowed if one unit is used only. If 2 or more units
are used it is required to mount the units vertically.
In case other equipment is present in the same rack, the AM/AMS unit should be
separated from this equipment by means of a heat baffle.
NOTE: Due to thermal reasons it is highly recommended to mount AC units vertically
(see section below).
Vertical rack mounting
Please observe the following rules for vertical rack mounting:
• A maximum of 10 units (2 blocks - 5 units) can be mounted within one rack. In
that case, a heat baffle must be placed in the middle of the rack as shown in the
figure below.
Figure A-3 Vertical mounting (AM/AMS, AC)
Rack
Heat Baffle
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
AM/AMS (AC)
bar
bar
bar
bar
Mounting rules
...................................................................................................................................................................................................................................