222 Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter B Parameter List
I/O
Mapping
(cont.)
324 40225 400225 AUX6 ASSIGN REG1 0 = Overload 0 Get/Set
1 = Undercurrent 0
2 = Jam 0
3 = Curr. Imbalance 0
4 = Short Circuit 0
5 = RTD-Wind Bear 0
6 = PTC 0
7 = GF-Res 0
8 = VAR 0
9 = Underpower 0
10 = Undervoltage 0
11 = Overvoltage 0
12 = Phase Reversal 0
13 = Power Factor 0
14 = Speed Switch 0
15 = GF-CB 0
325 40226 400226 AUX6 ASSIGN REG2 0 = Start Time 0 Get/Set
1 = Frequency 1 0
2 = Frequency 2 0
3 = RTD - Other 0
4 = RTD - Ambient 0
5 = PTC Error 0
6 = RTD Error 0
7 = MCM/CWE Error 0
8 = Comm Idle 0
9 = Comm Loss 0
10 = Remote Trip 0
11 = Comm Fault 0
12 = Latch Trip 0
13 = Reserved 0
14 = Reserved 0
15 = Reserved 0
Group
DeviceNet
Param No.
Modbus Register
Parameter Name Min Max Default
Scale
Factor
Units Access
Read (0x03h) Write (0x06h)