Rockwell Automation Publication 825-UM004D-EN-P - April 2012 223
Parameter List Chapter B
I/O
Mapping
(cont.)
326 40227 400227 AUX6 ASSIGN REG3 0 = RTD_Amb Warn 0 Get/Set
1 = SALARM 0
2 = Warning 0
3 = Load Ctl Upper 0
4 = Load Ctl Lower 0
5 = Timer 1 0
6 = Timer 2 0
7 = Short Ckt Warn 0
8 = Stopped 0
9 = Running 0
10 = Starting 0
11 = Star 0
12 = Delta 0
13 = Start 0
14 = Network 0
15 = Reserved 0
327 40228 400228 AUX6 ASSIGN REG4 0 = Overload Warn 0 Get/Set
1 = Undercurr Warn 0
2 = Jam Warn 0
3 = Curr. Imbal Warn 0
4 = RTD-W, B Warn 0
5 = Pwr Factor Warn 0
6 = GF-CB Warn 0
7 = GF-Res Warn 0
8 = VAR Warn 0
9 = Underpower Warn 0
10 = Undervolt Warn 0
11 = Overvolt Warn 0
12 = Spd Switch Warn 0
13 = Freq1 Warn 0
14 = Freq2 Warn 0
15 = RTD-OtherWarn 0
Group
DeviceNet
Param No.
Modbus Register
Parameter Name Min Max Default
Scale
Factor
Units Access
Read (0x03h) Write (0x06h)