General Data
Conformity and approvals for 1694-PM with 1694-PF
Ambient temperature (T
amb
) -25°...+60 °C (without condensation, cf. EN 60204-1)
Storage temperature -30°...+70 °C
Vibration resistance 3 g, test to IEC 60068-2-6 test Fc
Degree of protection
Operating area 1694-PM:
IEC 60529, DIN VDE 0470
IP30
EMC requirements
(EMC Directive, CE Logo)
Emitted interference: EN 61000-6-3
Noise immunity: EN 61000-6-2
Insulation co-ordination
(IEC 60934)
0.5 kV / pollution degree 2
Dielectric strength max. DC 30 V (load circuit)
Insulation resistance
(OFF condition)
n/a, only electronic disconnection
Modules mountable side by side
2
Rockwell Automation recommends to use ferrules for smaller diameter cables.
3
Class 2 only for Protection Modules
max. 36 channels allowed. Total current value shall be below 40 Amps.
(sample case: 36 channels refer to 1 Amp nominal current channels)
Dimensions (h x w x d) 12.5 x 80 x 98.5 mm
Weight approx. 60 g
Conformity CE Marking
RoHS compliant
China RoHS
WEEE
Morocco EMC
At the End of its life, this equipment should be collected separately from any unsorted municipal waste.
Approvals UL 2367 RA File # E350272 current rating range: 1A… 10A
UL 1310 RA File # E350272 current rating range:
NEC Class2
3
1A, 2A, 3A, 4A
cULus508 RA File # E56639 current rating range: 1A… 10A
listed
Terminals
Push-in terminal PT 2.5
wire stripping length
LOAD+
0.14mm
2
to 2.5mm
2
, flexible
AWG24 – AWG14 str.
2
8mm to 10mm
Mounting temperature +5°… +60°C
Publication 1694-IN002D-EN-E - June 2020 DIR 10005220601 (Version 03)
User Manual: Bulletin 1694 Electronic circuit protection for 24V DC
4
Humidity: 96 hrs / 95% RH RH/40 °C to IEC 60068-2-78-Cab climate class 3K3 to EN 60721
Corrosion
Only 1694-DM and 1694-PF
accessories
96hrs. in 5% salt mist to IEC 60068-2-11 test Ka