EasyManua.ls Logo

Allen-Bradley Bulletin 1694 - Distribution Module (1694-DMx) Data; DMx Operational Data and Dimensions; Power Feed Module (1694-PFx) Data; PFx Operating and Auxiliary Data

Allen-Bradley Bulletin 1694
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data for Power Feed Module 1694-PFx
Data for Distribution Module 1694-DMx
Publication 1694-IN002D-EN-E - June 2020 DIR 10005220601 (Version 03)
User Manual: Bulletin 1694 Electronic circuit protection for 24V DC
8
Vibration resistance 3 g, test to IEC 60068-2-6 test Fc
Degree of protection
terminal area 1694-PF, 1694-DM:
IEC 60529, DIN VDE 0470
IP20
EMC requirements
(EMC Directive, CE Logo)
Emitted interference: EN 61000-6-3
Noise immunity: EN 61000-6-2
Insulation co-ordination
(IEC 60934)
0.5 kV / pollution degree 2
Dielectric strength max. DC 30 V (load circuit)
Dimensions
Operational Current
Operating voltage U
B
Dimensions (h x w x d)
Weight approx.
Max. 20 A in total. Max. 10 A per terminal
0V - DC 24V (0 ... 30 V)
12.5 x 80 x 98.5 mm
60 g
12.5 x 80 x 98 mm
Operating voltage U
B
DC 24 V (min. 18 V, max. 30 V)
(no battery-buffered applications)
Reverse polarity protection Yes, without load
Closed current I
0
normal condition: typically 10 mA (min. 6,5 mA; max. 11,8 mA)
Auxiliary contact
potential-free
only in 1694-PFA1244
max. DC 30 V/0.5 A, min. 10 V/1 mA
Group signalling Si terminal:
Si (13) / Si (14)
Normal condition:
Auxiliary contact N/O
Auxiliary contact closed
Trip condition: coming from all protection modules
- when ON, load output ON
- when OFF, load output OFF
auxiliary contact open
Coming from one or more protection modules
- after disconnection due to overload or short circuit
- after undervoltage release of operating voltage in ON condition with auto reset
- at no operating voltage U
B
in supply module
Insulation coordination
Insulation coordination
0.5 kV / pollution degree 2
For 1694-PF3L4C, 1694-PF2L4S: 0.8 kV / pollution degree 2
Operating current I
B
Dimensions (h x w x d)
1694-PFx: Max. 40 A
12.5 x 80 x 98 mm
0.5 kV / pollution degree 2
For 1694-DM1L2, 1694-DM2L2: 0.8 kV / pollution degree 2