7–11Set Up or Simulate Rotary Cam Limit Switches
Publication
65566.5.1 - October 1996
Faults Associated with Processor B
B168/ Suggested Message Cause of Fault Effect of Fault How to Correct the Fault
106* Illegal RCLS Combination Software/hardware cams produced
invalid combination.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
107* Forward Transition
from Top
Software/hardware cams did not
go from top to downstroke.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
108* Forward Transition
from Downstroke
Software/hardware cams did not
enter upstroke.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
109* Forward Transition
from Upstroke
Software/hardware cams did not
enter near top zone.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
113* Forward Shaft Position
Transition Faults
Any of 107109 detected. Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
114* ACAM Upstroke ACAM did not cycle in upstroke. Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
121* Brake Monitor Cam Mis
match Between Processors
Processor A sees the BCAM while
processor B does not.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
122* Takeover Cam Mismatch
Between Processors
Processor A sees the
TCAM while processor B does not.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
123* Antirepeat Cam Mismatch
Between Processors
Processor A sees the ACAM while
processor B does not.
Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
124* Cam Mismatch Fault Any of 121123 detected. Press will stop or not run in
single or continuous mode.
Check software cam logic or hardware
cams for proper operation or settings.
* To clear this latched fault bit, you must turn the modeselect switch to OFF.