Appendix
B
Publication
65566.5.1 - October 1996
Feedback Timing Diagrams
We define the controller’s feedback response time for these signals:
• triac and valve-stem feedback
(where valve-stem feedback pertains to main, auxiliary,
and/or micro-inch valves with external fault detection)
• motion detector feedback
When PLC-5/x6 processors command triacs ON or OFF, they check
that feedback signals (triac, valve stem, and motion detector) have
turned ON or OFF in the order shown and within the times shown.
This feedback
signal:
Has a turnon time measured
from offtoon transition of:
and a turnoff time measured
from ontooff transition of:
Triac [ 1 ] triac command [ 4 ] triac command
Valvestem [ 2 ] triac feedback
Motion Detector Turns ON before upstroke
(Before BCAMs turn OFF)
Triac Command
ON
OFF
Triac Feedback
ON
OFF
01 sec
Valve
Stem Feedback
OFF
01 sec
[1]
[4]
03 sec
[4]
Motion Detector must turn ON before upstroke
(before Brakemontor cams (BCAMs) turn OFF)
Offtoon transition Ontooff transition
position dependent Time dependent
ON
OFF
01 sec
01 sec
[1]
[4]
If and when a PLC-5/x6 processor detects that a triac or feedback
signal has not turned ON or OFF within the times shown, it trips
seal relay output to remove power from the wiring arm of
1771-OD16 output module.
If your main valves have external fault-detection with valve-stem
switches and you configured for valve-stem feedback, you have two
options for the other solenoid valve inputs:
• they also must have external valve-stem switches and feedback, or
• if they have internal fault detection, you must simulate external
valve-stem feedback for them (See wiring drawings 8 and 9)
Timing Diagrams for
Control System Feedback