Rockwell Automation Publication 193-UM015E-EN-P - October 2015 187
Operating Modes Chapter 5
To change between Local and Remote control mode press and release the “Local/
Remote” button on the E300 Operator Station. The LED above “Local/Remote”
button illuminates yellow in Local control mode and red in Remote control
mode.
The E300 issues a trip or warning event if the E300 Operator Station disconnects
from the base relay.
The reset button of the E300 Operator Station is enabled for this operating
mode.
Rules
1. Available for Control Module firmware v5.000 and higher.
2. Output Pt00 Assignment (Parameters 202) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter
186)
• Operator Station must be enabled in Mismatch Action (Parameter
233)
• An operator station must be selected in Operator Station Type
(Paramete
r 224)
Or
• Option Match Warning must be enabled in WarningEnableC
(Paramete
r 192)
• Operator Station must be disabled in Mismatch Action
(Parameter 233)
• An
operator station must be selected in Operator Station Type
(Paramete
r 224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
The E300 relay’s Output Relay 0 is wired as a control relay in which the relay is
controlled by the communication network and opens when a trip event occurs.
The Non-reversing Starter (Network & Operator Station) operating mode uses
the value in network tag LogicDefinedPt00Data to control the starter. When
communication is restored between an automation controller and the E300,
the starter energizes if the value in LogicDefinedPt00Data is set to 1.