Rockwell Automation Publication 193-UM015E-EN-P - October 2015 333
Protective Trip and Warning Functions Chapter 6
Jam Warn Level
Jam Warn Level (Parameter 254) allows you to define the current at which the
E300 relay indicates a warning. It is user-adjustable from 50…600% for the FLA
Setting (Parameter 171).
Table 253 - Jam Warning Level (Parameter 254)
Underload Protection
Motor current less than a specific level may indicate a mechanical malfunction in
the installation, such as a torn conveyor belt, damaged fan blade, broken shaft, or
worn tool. Such conditions may not harm the motor, but they can lead to loss of
production. Rapid underload fault detection helps to minimize damage and loss
of production.
The E300 relay can monitor for this condition with its Underload Trip and
Warning function to detect for a rapid underload fault to minimize damage and
loss of production.
Underload Inhibit Time
Underload Inhibit Time (Parameter 255) allows you to inhibit an underload trip
and warning from occurring during the motor starting sequence. It is adjustable
from 0…250 s.
Table 254 - Underload Inhibit Time (Parameter 255)
Default Value 150
Minimum Value 50
Maximum Value 600
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 1
Units %FLA
IMPORTANT
The Jam Warning function does not include a time delay feature. Once the Jam
Inhibit Time has expired, the Jam Warning indication is instantaneous.
Default Value 10
Minimum Value 0
Maximum Value 250
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units Seconds