Rockwell Automation 442G-IN001C-EN-P – October 2015
Multi-functional Access Box Installation Instructions 3
Dimensions [mm
(in.)]
Electrical Connection
The electrical connections must either be isolated from the mains
supply by a safety transformer according to IEC 61558-2-6 with
limited output voltage in the event of a fault, or by other
equivalent isolation measures.
For detailed information on the electrical connection, refer to the
user manual.
Terminal Assignments and Wiring
Connection of Cover Controls and Indicators
113.5 (4.47)
104 (4.09)
40
(1.57)
40
(1.57)
15
(0.59)
33.5
(1.32)
40
(1.57)
106
(4.17)
155.3 (6.11) 130 (5.12)
4 (0.16)
114
(4.49)
111
(4.37)
83
(3.27)
<51>
(2.01)
40
(1.57)
62.5
(2.46)
M20 x 1.5 (4x)
19.2
(0.76)
289.3 (11.39)
10-45.1
(0.39-1.78)
S 1 S 2
4S3S
6 (0.24)
37.5
(1.48)
1 (0.04)
21
(0.83)
30
(1.18)
19
(0.75)
60
(2.36)
47.5
(1.87)
87654321
87654321
Terminal assignment
X5 X4
X3
optional cover function*
X2
IMM
IMP
*
0V
UA
OT
OL
OI
0V
UB
OD
654321
FI1B
*
FO1A
FO1B
RST
FI1A
654321
2
3
4
5
1
11
10
9
8
7
12
18
19
15
6
17
16
13
14
H2
1 3
S1
725 43
S3
H3
0V
2
X2
6 85 41
H4
S4
6
S2
A
U (24V)
X3
1
19-pin mating cordset Cat. No. 889M-F19RM-*
2
The lock modules are factory preset for standalone operation. See the user
manual for configuring the device for series operation (cable entry models only).
3
On QD models, terminal X5.6 is connected internally to terminal X3.4.
For models with E-stop and three push buttons (lock module
catalog numbers ending in –C04):
M23 QD
19-Conductor
Cordset
1
MAB Internal
Wire Color Terminal Function Description
1 Violet Brown X3.7 IMP Lock command
2 Red Yellow X2.1 S1.A1 E-stop circuit A
3 Grey White X2.2 S1.B1 E-stop circuit B
N/A N/A No Connection X4.1 FI1A
Safety input channel A
2
N/A N/A No Connection X4.2 FI1B
Safety input channel B
2
4 Red/Blue Green X4.4 FO1A
Safety output channel A, ON
when guard is locked
5 Green/Black Grey X4.5 FO1B
Safety output channel B, ON
when guard is locked
6 Blue Black X3.5 0V Connected internally to X5.5
7 Grey/Pink Pink X4.6 RST
Reset, apply 24V for at least
3 seconds
8 White/Green Violet X5.2 OT
Bolt monitoring output, ON
when guard is closed and
bolt is extended
9 White/Yellow Brown/Green X5.4 OI
Fault diagnostic, ON when
the switch is in a fault state
10 White/Grey Red/Blue X2.3 S1.A2 E-stop circuit A
11 Black Grey/Pink X2.4 S1.B2 E-stop circuit B
N/A N/A No Connection X2.6 S1 Aux. E-stop monitoring contact
12 Green/Yellow N/A N/A GND Connector housing GND
13 Yellow/Brown Grey/Brown X2.7 S2
Push button switching
element (S2)
14 Brown/Green White/Yellow X3.1 H2 Push button LED (H2)
15 White Yellow/Brown X3.2 S3
Push button switching
element (S3)
16 Yellow White/Grey X3.3 H3 Push button LED (H3)
N/A N/A No Connection x5.1 OD
Door monitoring output, ON
when the door is closed
17 Pink White/Green X5.3 OL
Lock Monitoring output, ON
when guard is locked
18 Grey/Brown Yellow/Black X3.8 IMM Reserved for future use
19 Brown Blue
X3.4 UA
Power for solenoid and
monitoring outputs
X5.6 UB Power for safety outputs
17 Pink White/Green X2.5 S4
Push button non-switching
element (S4)
18 Grey/Brown Yellow/Black X2.8 H4 Push button LED (H4)
Connection of this device with a conduit is not allowed. The connection
method needs to consist of flexible cord that is connected to the product
with a UL Listed cable gland suitable for 22…17 AWG wire sizes (for
example, Type HSK-KM20 x 1.5 manufactured by HummelAG).
IMPORTANT