Rockwell Automation Publication 7000-TG002J-EN-P - March 2015 83
Warning Messages Chapter 2
X X X X X X 2U1A Offline 286 PWM RECTIFIER SGCT WARNING
This warning occurs if Redn Dvc Rec option is selected in
HardwareOptions1 (P141). This SGCT device on the rectifier side
was detected to be faulted after the input contactor was closed
or following a start command or following a drive reset.
• After isolating the drive from medium voltage, be sure that the
device, IGDPS power supply and the fiber-optic signals are not
damaged.
• Complete a resistance check per the instructions in the manual.
NOTE: SGCTs may not have completely shorted, and still could read
in the k range. Any devices with low suspect readings should be
changed.
• Check the LED status of the SGCT gate driver card for abnormal
readings.
• Complete a Gating Test mode check on the devices.
• Verify the associated 20V power supply is powered and active.
• Verify all the power connections to the SGCT firing card are seated
properly.
NOTE: There is only the Redundant option available on the Rectifier,
and only on 6P drives (SCR or PWM). You cannot have N-1 operation
on the rectifier since we cannot control the line voltage.
X X X X X X 2U1B Offline 292
X X X X X X 2U1C Offline 298
X X X X X X 2U4A Offline 289
X X X X X X 2U4B Offline 295
X X X X X X 2U4C Offline 301
X X X X X X 2V3A Offline 288
X X X X X X 2V3B Offline 294
X X X X X X 2V3C Offline 300
X X X X X X 2V6A Offline 291
X X X X X X 2V6B Offline 297
X X X X X X 2V6C Offline 303
X X X X X X 2W2A Offline 287
X X X X X X 2W2B Offline 293
X X X X X X 2W2C Offline 299
X X X X X X 2W5A Offline 290
X X X X X X 2W5B Offline 296
X X X X X X 2W5C Offline 302
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Warning Message Warning
Code
Description Recommended Action(s)