46 Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 23 - 2-Wire Control on 11-Series I/O Module
Non-Reversing - Internal Supply
11-Series I/O Module TB1
Set Direction Mode
Port 0: P308 [Direction Mode] = 2 “Rev Disable”
Set Selection
Port 0: P163 [DI Run] = Port 4 (or port where yo
ur 11-Series I/O Module is installed), See page 10: P1 [Dig In Sts], bit 0 = Input 0
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page
10: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
Jumpers set to internal supply source.
Reversing - External Supply
11-Series I/O Module TB1
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Set Selection
Port 0: P164 [DI Run Forward] = Port 4 (or port where your 11-Series I/O Module is installed), See page 10: P1 [Dig In Sts], bit 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port 4 (or port where y
our 11-Series I/O Module is installed), See page 10: P1 [Dig In Sts], bit 1 = Input 1
View Results
Port 4 (or port where your 11-Series I/O Module is installed), See page
10: P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
Jumpers set to external supply source.