5-6 Setpoint Programming and Operation
Setpoint Low Limit The value being used as a reference to
deactivate the setpoint for over comparisons,
or to activate the setpoint for under
comparisons.
0 to 10,000,000 Depends on type 0
Setpoint Action Delay The minimum time in seconds that the
setpoint limit must be exceeded continuously
before the setpoint will trigger.
0 to 3600 Sec (M4, M5) 0
0 to 30,000 0.1 Sec (M6, M8)
Setpoint Release
Delay
The minimum time in seconds that the
setpoint limit must not be exceeded
continuously before the setpoint releases.
0 to 3600 Sec (M4, M5) 0
0 to 30,000 0.1 Sec (M6, M8)
Setpoint Action Type The action that occurs when the setpoint is
triggered.
0 to 32 (see details in
Table 5.3)
0
Clear Accumulated
Time
Clear the time accumulator for this setpoint Yes
No
N/A
Table 5.1 Setpoint Configuration
Parameter Name Parameter Description Range Units Default