Publication 1404-UM001D-EN-E - October 2004
8-14 Advanced Features
Figure 8.1 Sag and Swell
The pre-defined setpoint configuration for the detection of sag and
swell is based on the IEEE-1159 standard. Although the default
setpoint configuration is applicable as-is for many sag and swell
applications, it may be necessary to alter the setpoint configuration to
adjust the unit’s sensitivity to sags and swells for your particular
application.
Setpoint #19 is setup to detect voltage sag and has the following
configuration data:
Type = Voltage Sag
Evaluation condition = Under forward
High Limit = 90% Nominal System Voltage
Low Limit = 90% Nominal System Voltage
Action delay = 0
Release delay = 0
Output action = Capture oscillograph
Setpoint #20 is setup to detect voltage swell and has the following
configuration data:
Type = Voltage Swell
Evaluation condition = Over forward
High Limit = 110% Nominal System Voltage
Low Limit = 110% Nominal System Voltage
Action delay = 0
Release delay = 0
Output action = Capture oscillograph