Publication 1404-UM001D-EN-E - October 2004
Advanced Features 8-19
Figure 8.2 Transient Capture
Transient Analysis Configuration
Perform a table write to Table A.43 Transient Analysis
Configuration/Read-Back Select to configure transient analysis. This
read/write table of 13 floating-point elements contains the following
configuration, command and read-back select parameters:
Password: required for configuration and command. Use a valid
password or -1 for read-back select. Range 0000 to 9999, default
0, returns -1
DeviceNet unique write identifier: range -32,768 to 32,767,
default 0
Capture number: selects a capture for read-back. Range 0 to 6,
default 1
Cycle number: selects a cycle for read-back. Range 1 to 12,
default 1
Read-back mode: 0 = auto-increment mode; cycle number
increments after each read of Table A.44. 1 = manual-increment
mode; only mode supported by DeviceNet and Ethernet
communications. Default 0
Detection mode: selects channels to monitor. 0 disables transient
detection, 1 = voltage channels only, 2 = current channels.
Default 1
Auto-threshold set command: 0 = do nothing, 1 = set threshold.
Default 0
Auto-threshold set duration: range: 1 to 3600 seconds, default 10