Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-9
Table A.6 Advanced Device Configuration
CSP File No. N12
Remote I/O BT 26
CIP Assy. Inst. 8 (Write), 9 (Read)
No. of Elements 25
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
0 40201 Password 0 to 9999 - 0 Required to change configuration data.
Returns -1
1 40202 New password 0 to 9999 - -1 -1 = no action; 0 to 9999 = new password;
returns -1
2 40203 Demand period length -99 to
+99
Min 15 Refer to Demand Calculation on page 3-9
3 40204 Number of demand periods 1 to 15 - 1
4 40205 Predicted demand type 0 to 2 - 0 0 = instantaneous; 1 = 1st order; 2 = 2nd order
5 40206 KYZ control source 0 to 8 - 7 0 = None (forcing
only)
1 = Wh Forward
2 = Wh Reverse
3 = VARh Forward
4 = VARh Reverse
5 = Vah
6 = Ah
7 = Setpoints
8 = Discrete control (RIO,
DeviceNet)
6 40207 KYZ pulse output scale 1 to
30000
- 10 Refer to Relay and KYZ Output Operations on
page 6-1
7 40208 KYZ pulse output width 0, 40 to
2000
mSec 0 0 = KYZ-style transition
40 to 2000 = pulse duration
8 40209 Relay control source 0 to 8 - 7 Same choices as KYZ control source
9 40210 Relay pulse output scale 1 to
30000
- 10 Refer to Relay and KYZ Output Operations on
page 6-1
10 40211 Relay pulse output width 0, 40 to
2000
mSec 100 0 = KYZ-style transition
40 to 2000 = pulse duration
11 40212 RMS resolution 0 to 1 - 0 (M4)
1 (M5, 6 or 8)
0 = Nominal
1 = High
12 40213 RMS result averaging 0 to 1 - 0 (M4)
1 (M5, 6 or 8)
0 = No averaging.
1 = Average of the last 8 results
13 40214 Frequency averaging 0 to 1 - 1 0 = none; 1 = last 8 cycles
14 40215 Restore factory default
config
0 to 1 - 0 0 = No action 1 = Restore factory default settings
15 40216 Clear status input counters 0 to 3 - 0 0 = No action
1 = Clear counter #1
2 = Clear counter #2
3 = Clear both
16 40217 Wdog action 0 to 1 - 1 0 = Restart, log an event and halt operation
1 = Restart, log an event and resume
Refer to Watchdog Timeout Action on page 3-28.