Publication 1404-UM001D-EN-E - October 2004
Product Description 2-7
DeviceNet Optional Communications
A catalog number ending in -DNT specifies a Powermonitor 3000 with
a DeviceNet port in addition to the native RS-485 port. The DeviceNet
option permits concurrent use of both communications ports. The
DeviceNet port has the following performance features:
Adapter class device
Four baud settings: 125k, 250k, 500k and AutoBaud
Remotely settable baud rate
Cable length up to 500 meters maximum
Node capacity up to 64 nodes including master
Remotely settable node address
Shielded twisted-pair media containing both signal and power
conductors
Update rates for I/O channel: 100 mSec minimum
Update rates for explicit messaging: 250 mSec minimum
Configurable I/O channel assembly instance: six parameters
default, twenty-three maximum
Configurable explicit assembly instance: seventeen parameters
default, twenty-three parameters maximum
Explicit assembly instances for access to all data
Two I/O assembly instances
May be reset remotely through Identity Object
Support for up to four concurrent clients
Supports DeviceNet heartbeat facility
Ethernet Optional Communications
A catalog number ending in -ENT specifies a Powermonitor 3000 with
one active 10BaseT Ethernet communication port in addition to the
native RS-485 port. The Ethernet port has the following performance
features:
Connect to Allen-Bradley PLC-5E, SLC 5/05, ControlLogix
Ethernet Bridge and the 1761-NET-ENI module products
Built-in Internet web page support
Compatible with RSPower32, RSEnergyMetrix, RSView32 and
RSTrend™ software
Ethernet communication rate: 10Mbps (Series A)
10/100Mbps (Series B)
Allen-Bradley HMIs