Publication 1404-UM001D-EN-E - October 2004
A-26 Powermonitor 3000 Data Tables
Table A.18 Setpoint Setup/Read-Back Select and Status
CSP File No. N23
Remote I/O BT 22
CIP Assy. Inst. 24 (Write), 25 (Read)
No. of Elements 16
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
0 40701 Password 0 to 9999 - 0 Required for configuration, -1 for readback
select, returns -1.
1 40702 Setpoint number 1 to 10 (M4, M5)
1 to 20 (M6, M8)
- - Refer to Writing Setpoint Configuration Using
Communications on page 5-11.
2 40703 Read-back mode 0 to 1 - 0
3 40704 Setpoint type 0 to 52 -
0
(1)
4 40705 Evaluation condition 0 to 5 - 0
5 40706 High limit
Integer
0 to 9999 Depends
on
setpoint
type
0
(1)
6 40707 High limit Exponent -4 to 21
0
(1)
7 40708 Low limit
Integer
0 to 9999
0
(1)
8 40709 Low Limit Exponent -4 to 21
0
(1)
9 40710 Action delay 0-3600 (M4, M5)
0-30000 (M6, M8)
Seconds
(M4, M5)
.1 Sec
(M6, M8)
0
10 40711 Release delay 0-3600 (M4, M5)
0-30000 (M6, M8)
Seconds
(M4, M5)
.1 Sec
(M6, M8)
0
11 40712 Output action 0 to 32 (M4, M5)
0 to 43 (M6, M8)
-
0
(1)
12 40713 Status 0 to 1 - 0
13 40714 Accumulated time
Integer
0 to 9999 Seconds -
14 40415 Accumulated time
Exponent
-1 to 21 - -
15 40716 Clear time
accumulator
command
0 to 1 - 0
(1) On the M6 and M8, setpoint #19 and #20 default to detect voltage sag and voltage swell. See Sag and Swell, page 8-13