Powermonitor 3000 Data Tables A-31
Table A.21 Trend Log Configuration/Read-Back Record Select
CSP File No. N24
Remote I/O BT 34
CIP Assy. Inst. 26 (Write), 27 (Read)
No. of Elements 26
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 40801 Password 0 to 9999 0 Required for configuration, -1 for readback select, returns -1.
1 40802 DeviceNet unique write
identifier
-32768 to
32767
0 Refer to DeviceNet Unique Write Identifier on page 4-36.
2 40803 Reserved 0 0 Must be 0 on a write; returns 0
3 40804 Read-back mode 0 to 6 2 Refer to Setting up the Trend Log on page 7-11, and Reading
Data from the Trend Log on page 7-12.
4 40805 Logging interval -1 to 3600 900
(15 min)
Expressed in seconds
-1 = synchronize logging with demand interval
0 = disable periodic logging
5 40806 Logging mode 0 to 1 0 0 = Overwrite
1 = Fill and hold
6 40807 Clear trend log command 0 to 1 0 0 = no action
1 = clear trend log; returns 0
7 40808 Total records logged x 1000 0 to 999 - Number of records = element 7 x 1000 + element 8
8 40809 Total records logged x 1 0 to 999 -
9 40810 Reserved 0 - Must be 0 on a write; returns 0
10 40811 Parameter #1 selection 1 to 301 122 Refer to Setting up the Trend Log on page 7-11.
Defaults:
Parameter 1: 122, Net Kilowatt-hours
Parameter 2: 126, Net kVAR-hours
Parameter 3: 100, Demand watts
11 40812 Parameter #2 selection 0 to 301 126
12 40813 Parameter #3 selection 100
13 40814 Parameter #4 selection 0
14 40815 Parameter #5 selection
15 40816 Parameter #6 selection
16 40817 Parameter #7 selection
17 40818 Parameter #8 selection
18 40819
Parameter #9 selection
(1)
0 to 301 0
19 40820 Parameter #10 selection
20 40821 Parameter #11 selection
21 40822 Parameter #12 selection
22 40823 Parameter #13 selection
23 40824 Parameter #14 selection
24 40825 Parameter #15 selection
25 40826 Parameter #16 selection
(1) For DeviceNet Powermonitors you may configure parameters 9 through 16 but Table A.22 will return only the first 8 parameters.