Publication 1404-UM001D-EN-E - October 2004
A-38 Powermonitor 3000 Data Tables
2 30903 ••Timestamp of event; Year
Month/day
Hour/minute
Second/hsec
1998 to 2097 Refer to Expressing Data in Data Tables on
page 4-18.
3 30904 •• 0101 to 1231
4 30905 •• 0000 to 2359
5 30906 •• 0000 to 5999
6 30907 ••Event type 0 to 19 Refer to Table A.29 List of Event Types
7 30908 ••Event code - Refer to Reading Data from the Event Log
Using Communications on page 7-5
8 30909 ••Setpoint type 0 to 52
9 30910 ••Setpoint evaluation condition 0 to 5
10 30911 ••Setpoint level integer
exponent
0 to 9999
11 30912 •• -21 to 21
12 30913 ••Setpoint action/release delay 0 to 3600 (M4, M5)
0 to 30000 (M6, M8)
13 30914 ••Setpoint action 0 to 32 (M4, M5)
0 to 43 (M6, M8)
14 30915 ••Sustain limit timer integer
exponent
0 to 9999
15 30916 •• -4 to 21
16 30917 ••Capture identifier 0 to 999
17 30918 Event Text Available 0 to 1 Refer to Event Log User Comment Field
(M8 only) on page 7-6
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name Range Comment
Table A.28 Status Error Codes
Bits Hex Description
bit 0 0001h Master Module code flash status
bit 1 0002h Master Module data flash status
bit 2 0004h Master Module RAM Status
bit 3 0008h Reserved for factory use
bit 4 0010h Master Module NVRAM status
bit 5 0020h Master Module data acquisition status
bit 6 0040h Master Module real time clock status
bit 7 0080h Reserved for factory use
bit 8 0100h Reserved for factory use
bit 9 0200h Display Module status
bit 10 0400h Master Module watchdog timer status
bit 11 0800h Master Module optional communications status
bit 12-15 1000h -8000h Reserved for factory use