Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-49
Table A.39 Oscillograph Configuration/Read-Back Data Select
CSP File No. N39
Remote I/O BT 15
CIP Assy. Inst. 46 (Write), 47 (Read)
No. of Elements 11
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type M6, M8 only
Applies to: Table A.40 Oscillograph Results
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 - Password 0 to 9999 0 Required for configuration, -1 for readback
select, returns -1.
1 - Capture No. 0 to 8 (M6)
0 to 2 (M8)
1 Refer to Configuring Oscillography on page 8-1
2 - Channel No. 1 to 7 1
3 - Block No. See page 8-3 1
4 - Read-back mode 0 to 2 0
5 - Clear/trigger command 0 to 10 0
6 - Capture type -1 to 5 0
7 - % Pre-trigger 0 to 100 90
8- Reserved 0 0
9 - Capture clear status 0 to 255 -
10 - Capture ready status 0 to 255 -