EasyManua.ls Logo

Allen-Bradley Powermonitor 3000 - Page 62

Allen-Bradley Powermonitor 3000
356 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1404-UM001D-EN-E - October 2004
4-2 Communications
Native RS-485 Communications
Your Powermonitor 3000 is set up to communicate via its native
RS-485 port when you first power it up, except for units with an
optional RS-232 communication port. The communications
configuration includes the following parameters:
Protocol: Allen-Bradley DF1 half-duplex slave, Modbus RTU
slave, or auto-sense. Default auto-sense
Data rate: Range 1200, 2400, 4800, 9600, 19,200 baud. Default
9600
Delay: Range 0 to 75 mS, 10 mS default
Data Format: 8 data bits, 1 stop bit, no parity, odd parity or
even parity. Default no parity
Node address: Range 1 to 247, default is the same value as the
unit ID listed on the nameplate
Inter-character timeout: Range 0 to 6553 msec. Default 0 (= 3.5
character times)
The Delay parameter is the time the Powermonitor 3000 waits before
its response to an external request. Certain communications
equipment requires such a delay for reliable operation.
To change your native port configuration, use the Display Module
under the PROGRAM > NATIVE COMMUNICATIONS menu.
You may connect your Powermonitor 3000 into an RS-485 network
with up to 32 nodes connected with 2-conductor shielded twisted pair
cable with a maximum cable length of 1,219 meters (4,000 ft.). The
maximum data rate supported by the Powermonitor 3000 is 19.2
Kbaud. You must use a device configured as a master to communicate
with this port. Error checking method is CRC (Cyclic Redundancy
Check). All devices on the RS-485 network must be set at the same
data rate.
TIP
The native communications port does not support
Data Highway 485 (DH-485) communications.
Although DH-485 uses the RS-485 physical media, its
protocol is not compatible with the DF1 protocol.

Table of Contents