EasyManua.ls Logo

Allen-Bradley Ultra1500 2092-DA1 - Group 3 Parameters

Allen-Bradley Ultra1500 2092-DA1
204 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 2092-UM001D-EN-P — July 2005
D-22 Ultra1500 Operator Interface
Group 3 Parameters
Group 3 Parameters provide position control settings.
Pr-3.00 Follower Configuration
Data Size: 4 digits
Digit 0: Command Type
Range: Value Description
0x0 CW + CCW, Positive logic
0x1 CW + CCW, Negative logic
0x2 Pulse Line + Sign, Positive Logic
0x3 Pulse Line + Sign, Negative Logic
0x4 A Phase + B Phase, Positive Logic
0x5
A Phase + B Phase, double input
multiplication, Positive Logic
0x6
A Phase + B Phase, quadruple input
multiplication, Positive Logic
Default: 0x0
Note:
For values 0x4, 0x5, and 0x6, Motor Counts = :
Master Lines * MULT * [(4 * Pr-3.01)/Pr-3.02]
Where the multiplier (MULT) is 1, 2, and 4 for values 0x4, 0x5,
and 0x6 respectively.
Applicable Operating Mode: Follower
Digit 1: Controller Output Type
Range: Value Description
0 Line Drive
1 Open Collector
Default: 0
Applicable Operating Mode: Follower
Digit 2: Encoder Output Forward Direction
Range: Value Description
0
During Forward Rotation, Encoder
Output Phase A have a lead of 90× over
Phase B.
1
During Forward Rotation, Encoder
Output Phase B have a lead of 90× over
Phase A.
Default: 0
Applicable Operating Mode: All
Digit 3: Reserved

Table of Contents