and type of washers that are connected to the water re-use sys-
tem. The maximum pump pressure is 1
16 psi [8 bar] .
It is advisable to install a level switch. This level switch must be
connected to the microprocessor by means of a potential-free
contact. Refer to Figure 22 .
CHM2560N_SVG
7
6
5
4
3
2
1
1. L
2. Level switch
3. K1
4. Terminal A
5. Terminal B
6. K1
7. N
Figure 22
The relay contact K1 has to close when the water level is too low.
Terminal B is positioned on the left side, in the lower part of the
microprocessor. Terminal A is positioned directly above Terminal
B. The microprocessor is positioned inside the washer. If the
"Check signal recycle" parameter is set to "yes" in the configura-
tion menu, the timer will send a signal if the water level of the
reuse tank is too low.
Electrical Installation Requirements
NOTE: Read Important Safety Instructions first.
IMPORTANT: The machines are designed and manufac-
tured for a voltage range. Refer to the serial plate for
voltage range information specific to your machine.
Make sure the supply voltage is always within the lim-
its specified. When you have long distances in the
electrical installation, it may be necessary to use big-
ger cables to reduce the voltage drop.
IMPORTANT: The machines are designed and manufac-
tured for 50/60Hz. Refer to the serial plate for frequency
information specific to your machine. Make sure the
frequency is always within the limits specified.
When a gravity drain is provided (no drain pump exe-
cution), the factory setting for the drain valve is 60Hz
for North American models and 50Hz for models out-
side of North America.
If the frequency at installation is different than the de-
fault setting, redirect the suppling voltage wire to the
appropriate frequency terminal at the drain valve.
North America Models Only:
IMPORTANT: This machine is not provided with a
Mains Disconnect Means. Suitable Mains Disconnect
Means must be provided during installation and by au-
thorized personnel in accordance with the Canadian
Electrical Code, Part 1 (CE Code), or (US) National
Electrical Code (NEC).
Models outside of North America:
IMPORT
ANT: When the machine is connected near a
large capacity power supply transformer (500kVA or
more, wiring length shorter than 32.81 ft [10 m] ) or
there is a power capacitor switch-over, a power supply
improving reactor must be installed. If you do not in-
stall this, the inverter may get damaged. Contact your
distributor for more information.
Models outside of North America: For electrical protection, if re-
quired by local regulations, there must be installed a residual cur-
rent device (RCD) and a circuit breaker in the electrical installa-
tion of the building (laundry switchboard). Refer to Figure 23 .
Electrical connections are made at the rear of the machine. The
machine must be connected to the proper electrical supply shown
on the serial plate on the rear of the machine, using copper con-
ductors only.
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
47 Part No. D1599ENR16