Function description
FK 3-12 spring operating mechanisms
For circuit
brea
kers
06.04.2011
48-020-212EN02
13/15
When motor
limit swit
ch 70.24
is actuated
by motor
limit swi
tch actuat-
ing cam 70.22 at the end of the closing movement, the motor circuit is
made and closing spring 70.25 is automatically recharged.
If no breaking operation has taken place during the charging process,
the circuit breaker is in steady operating state 4 at the end of the charg-
ing process. This is the normal operating state of all circuit breakers in
the electric power grid.
Circuit breaker
and operating
mechanism
are in
operating state
4.
Operating state
4: steady
Motor Closing
Opening
M
S
1
S
2
S
2
S
1
Y
1
Y
2
The
circuit breaker
is ready
for the
operating sequence
O-CO.