1. Introduction GEM80-400
Page 1-22 ALSPA GEM80-400 CONTROLLER TECHNICAL MANUAL Issue 3 04/99
Voltage Input
9032 Power Supply Module,
88-121V ac (110V nominal),
or 204-264V ac (240V
nominal) @47-63Hz OR 22-85V
dc (48V nominal). Maximum
wattage rating: 90W.
Note...Factory-set to 220V.
9017 Power Supply Module, 88-
264V ac @45-63Hz, or 88-250V dc;
maximum wattage rating: 260W.
9018 Power Supply Module, 19-
60V dc; maximum wattage
rating: 220W.
400S Controllers
A separate -15V supply is
required if Fast I/O module
require it.
Enhanced Controllers
Power supply modules type 8917
or 8918 are incorporated into
Fast I/O Subracks if a Fast I/O
Driver is fitted. Their maximum
wattage rating is 350W and 320W
respectively.
Temperature
Operating: 0 to 60°C, except with GEMLAN-D: 0 to 50°C.
Storage: -25 to 70°C.
Environment
and Tests
Tested to GEM 80 Environmental Standards. UL Approval, PLC
Specifications UL508 Industrial Control Equipment. CSA Approva
l,
C22-2-142 Process Control Specifications.
Mounting 19 inch (483mm) panel mounting conforms to IEC 297-1 (1975)
Dimensions of Panels and Racks.
Dimensions Height = 356mm; Width = 483mm; Depth = 332mm.
Weight Standard Subrack (empty) = 6.26kg; 400S and Enhanced AC
Subrack (empty) = 7.012kg; Enhanced DC Subrack (empty) =
6.122kg; Processor Module = 0.932kg; 9032 Power Supply Module
= 5.944kg; 9017 Power Supply Module = 5.306kg; 9018 Power
Supply Module = 5.39kg; 8917 Power Supply Module = 6.714kg;
8918 Power Supply Module = 6.794kg. Note...(1) Processor
Module includes screen, EPROM Memory Sub-module (0.062kg)
and FIP Sub-module (0.11kg). (2) Total weight of subrack
depends on number and type of I/O modules fitted.
1.13. Site Requirements
The area in which GEM
80 equipment is to be installed must fulfil the following
conditions:
(1)
An environment must be maintained as detailed in the 'Environment'
section of this chapter.
(2)
A power supply must be available as detailed in the 'Power Supply
Requirements' section of this chapter
(3)
Adequate access must be available for maintenance and
commissioning