M2x2/EN M/F User Manual
iSTAT M2x2
Page 47
ACCURACY (of range unless specified)
Class 0.5 RMS Current
(I
1
, I
2
, I
3
, Iavg, I
n
)
1A
5A
Class 0.5
Maximum Current 12.5A Class 0.5 (of reading)
75V L-N Class 0.5
250V L-N Class 0.5
RMS Line Voltage
(U
1
, U
2
, U
3
, Uavg)
500V L-N Class 0.5
Maximum Voltage 600V Class 0.5 (of reading)
120V L-L Class 0.5
400V L-L Class 0.5
RMS Phase-Phase Voltage
(U
12
, U
23
, U
31
, Uavg)
800V L-L Class 0.5
Frequency
Frequency (actual) 50/60 Hz 0.01Hz
Nominal Frequency Range 16….400 Hz 0.02 Hz
Power Angle 180…0…180° Class 0.5
Power Factor 1…0…+1
U = 50 … 120 % U
n
I = 2 % … 20 % I
n
I = 20 % … 200 % I
n
Class 2.0
Class 1.0
Maximum Demand Calculated from U and I Class 1.0
THD 5 to 500V Class 0.5
0 to 400% Class 0.5
Power
Active W Calculated from U and I Class 0.5
Reactive VAR: Q, apparent VA :
S
Calculated from U and I Class 1
Energy
Active Energy Calculated from U and I Class 1 to EN62053-21
Reactive Energy Calculated from U and I Class 2 to EN 62053-23
Note: All measurements are calculated with high harmonic signals. For
voltage up to 65 Hz, harmonics up to 32
nd
are measured.