M233 Compatible
Register map
M231 Compatible
Register map
Parameter Type
Start End Start End
Total Apparent Power S T5 30156 30157 30050 30051
Power Factor PF
1
T7 30166 30167 30060 30061
Power Factor PF
2
T7 30168 30169 30062 30063
Power Factor PF
3
T7 30170 30171 30064 30065
Total Power Factor PF T7 30164 30165 30058 30059
Power Angle U
1
−I
1
T2 30071
Power Angle U
1
−I
1
T17 30173
Power Angle U
2
−I
2
T2 30072
Power Angle U
2
−I
2
T17 30174
Power Angle U
3
−I
3
T2 30073
Power Angle U
3
−I
3
T17 30175
Power Angle atan2(Pt, Qt) T2 30070
Power Angle atan2(Pt, Qt) T17 30172
Angle U
1
−U
2
T2 30076
Angle U
1
−U
2
T17 30115
Angle U
2
−U
3
T2 30077
Angle U
2
−U
3
T17 30116
Angle U
3
−U
1
T2 30078
Angle U
3
−U
1
T17 30117
Frequency f T5 30105 30106
Frequency f (mHz) T1 30066
THD I
1
T16 30188 30118
THD I
2
T16 30189 30119
THD I
3
T16 30190 30120
THD U
1
T16 30182 30112
THD U
2
T16 30183 30113
THD U
3
T16 30184 30114
THD U
12
T16 30185 30115
THD U
23
T16 30186 30116
THD U
31
T16 30187 30117
Max Demand Since Last RESET
MD Real Power P (positive) T6 30542 30543
MD Real Power P (negative) T6 30548 30549
MD Reactive Power Q − L T6 30554 30555
MD Reactive Power Q − C T6 30560 30561
MD Apparent Power S T5 30536 30537
MD Current I
1
T5 30518 30519
MD Current I
2
T5 30524 30525