M2x2/EN M/F User Manual
iSTAT M2x2
Page 63
Rxxxxx are Modbus regi
ster numbers, see above and section 18.6 for descriptions.
It is suggested that these values are read regularly to ensure any changes made in the
settings are incorporated in the calculation.
As the nominal input ranges of the M2x2 are 500V and 5A, the Used voltage range and
Used Current range need to be set correctly to obtain the highest resolution normalized
values. These values are set using the QDSP software.
17.6 Register table for the basic settings
Register Content Type Ind
Values /
Dependencies
Min Max
P.
Level
40143 Connection
Mode
T1 0 No mode
1 5 2
1 1b - Single Phase
2 3b - 3 phase 3 wire
balanced
3 4b - 3 phase 4 wire
balanced
4 3u - 3 phase 3 wire
unbalanced
5 4u - 3 phase 4 wire
unbalanced
40144 CT Secondary T4 mA 2
40145 CT Primary T4 A/10 2
40146 VT Secondary T4 mV 2
40147 VT Primary T4 V/10 2
40148 Current input
range (%)
T16 10000 for 100%
5,00 200,00 2
40149 Voltage input
range (%)
T16 10000 for 100%
2,50 100,00 2
40150 Frequency
nominal value
T1 Hz
10 1000 2