Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 85/108
I2> :8765432
0100010
Assigning first alarm threshold for negative sequence
overcurrent (I2>) to the output relays; i.e. to output 3 &
7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tI2> :8765432
0100010
Assigning of the first trip threshold for negative
sequence overcurrent (I2>) to the output relays; i.e. to
output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I2>> :8765432
0100010
Assigning second alarm threshold for negative
sequence overcurrent (I2>>) to the output relays; i.e.
to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tI2>> :8765432
0100010
Assigning second trip threshold for negative sequence
overcurrent (I2>>) to the output relays; i.e. to output 3
& 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I2>>> :8765432
0100010
Assigning of the third alarm threshold for negative
sequence overcurrent (I2>>>) to the output relays; i.e.
to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
tI2>>> :8765432
0100010
Assigning of the third trip threshold for negative
sequence overcurrent (tI2>>>) to the output relays;
i.e. to output 3 & 7 (RL3 & RL7).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Therm :8765432
Alarm 1100010
Assigning thermal alarm to the output relays; i.e. to
output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Therm :8765432
Trip 1100010
Assigning thermal trip threshold to the output relays;
i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.
I< :8765432
1100010
Assigning threshold for undercurrent (I<) to the output
relays; i.e. to output 3, 7 & 8 (RL3, RL7 & RL8).
Setting choice: 1 assigns the output relay; 0 no
assignment.