6.4
Damp Heat
Steady State
Test
EN 60068-2-78, EN60068-2-30
Operating Temperature +40°C
Humidity 93%
Duration of Exposure 10 Days
EUT Condition Energised
6.5
Damp Heat
Cyclic Test
EN60068-2-30,
EN 60068-2-78
Lower Temperature C
Humidity 97%
Higher Temperature +55°C
Humidity 93%
Duration of Exposure 6 Cycle
Duration of Cycle 12 + 12 hrs.
EUT Condition Energised
6.6
Enclosure
Protection
EN 60529:2000
IP52 For Front
IP20 For Rare
EUT Condition Non-Energised