2.3.7 CT & VT RATIOS MENU
2.3.7.1 Edit settings
CT AND VT RATIOS
Password protected window for “CT AND VT RATIOS settings i.e.
Phase CT Primary and E/F CT Primary.
Press the Left arrow key () to move to the next option.
Password = 0000
Press the Edit Key, the number will start blinking.
Enter the previously set password by using the Plus / Up arrow key (+
/) or the Minus / Right arrow key (- /). The Password setting range
is 0000 to 9999. The Default Password is “0000”
After editing the Password press the Edit Key, the number will stop
blinking.
Press the Left arrow key () to move to the next option.
Phase CT Primary
00100 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Phase CT Primary can be set. The setting range is
from 1 to 30000 in steps of 1.
After editing the desired Phase CT Primary press the Edit Key, the
number will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option.
E/F CT Primary
00100 A
Press the Edit Key the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired E/F CT Primary can be set. The setting range is from 1
to 30000 in steps of 1.
After editing the desired E/F CT Primary press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
Phase CT Primary
00100 A
The window displays the first setting of the CT & VT RATIOS.
Press the Left arrow key () to move to the next option.
SET For Save
RESET For Cancel
Press the SET / Left arrow key () to SAVE the changes.
Press the RESET key to CANCEL the changes.
OK
When the SET / Left arrow key () is pressed the relay will SAVE the
changes and this window will flash for moment. The control will return to
the main menu.