Commissioning P54x/EN CM/La4
MiCOM P543, P544, P545 & P546
CM) 10-109
CM
3500 OVERCURRENT
Group 1 settings
Group 1
settings
Group 2
settings
Group 3
settings
Group 4
settings
350C I>2 Directional
350D I>2 Current Set
350E I>2 Time Delay
350F I>2 TMS
3510 I>2 Time Dial
3511 I>2 Reset Char
3512 I>2 tRESET
3513 I>3 Status
3514 I>3 Directional
3515 I>3 Current Set
3516 I>3 Time Delay
3518 I>4 Status
3519 I>4 Directional
351A I>4 Current Set
351B I>4 Time Delay
351C I> Char Angle
351D I> Blocking
3600 NEG. SEQ. O/C
Group 1 settings
Group 1
settings
Group 2
settings
Group 3
settings
Group 4
settings
3601 I2> Status
3602 I2> Directional
3603 I2> VTS
3604 I2> Current Set
3605 I2> Time Delay
3606 I2> Char Angle
3607 I2> V2pol Set
3700 BROKEN CONDUCTOR
Group 1 settings
Group 1
settings
Group 2
settings
Group 3
settings
Group 4
settings
3701 Broken Conductor
3702 I2/I1 Setting
3703 I2/I1 Time Delay