P54x/EN TD/La4 Technical Data
(TD) 2-12
MiCOM P543, P544, P545 & P546
TD
Phase Diff: Disabled/Enabled
Overcurrent: Disabled/Enabled
Neg Sequence O/C: Disabled/Enabled
Broken Conductor: Disabled/Enabled
Earth Fault: Disabled/Enabled
Sensitive E/F: Disabled/Enabled
Residual O/V NVD: Disabled/Enabled
Thermal Overload: Disabled/Enabled
Power Swing Block: Disabled/Enabled
Volt Protection: Disabled/Enabled
Freq Protection: Disabled/Enabled
df/dt Protection: Disabled/Enabled
CB Fail: Disabled/Enabled
Supervision: Disabled/Enabled
System Checks: Disabled/Enabled
Auto-Reclose: Disabled/Enabled
Input Labels: Invisible/Visible
Output Labels: Invisible/Visible
CT & VT Ratios: Invisible/Visible
Record Control: Invisible/Visible
Disturb Recorder: Invisible/Visible
Measure’t Setup: Invisible/Visible
Comms Settings: Invisible/Visible
Commission Tests: Invisible/Visible
Setting Values: Primary/Secondary
Control Inputs: Invisible/Visible
Ctrl I/P Config: Invisible/Visible
Ctrl I/P Labels: Invisible/Visible
Direct Access: Disabled/Enabled
InterMiCOM
64
Fiber: Disabled/Enabled
Function Key: Invisible/Visible
LCD Contrast: (Factory pre-set)
CT and VT ratios
P543 and P545 CT and VT ratio settings:
Main VT Primary: 100 V...1 MV
Main VT Sec'y: 80...140 V
C/S VT Primary: 100 V...1 MV
C/S VT Secondary: 80...140 V
Phase CT Primary: 1 A…30 kA
Phase CT Sec'y: 1 A/5 A
SEF CT Primary: 1 A…30 kA
SEF CT Sec'y: 1 A/5 A
MComp CT Primary: 1 A…30 kA
MComp CT Sec'y: 1 A/5 A
C/S Input:
A-N
B-N
C-N
A-B
B-C
C-A
A-N/1.732
B-N/1.732
C-N/1.732
Main VT Location: Line/Bus
CT Polarity: Standard /Inverted
CT2 Polarity: Standard /Inverted
SEF CT Polarity: Standard /Inverted
M CT Polarity: Standard /Inverted
VTs Connected: Yes/No
P544 and P546 CT and VT ratio settings :
Main VT Primary: 100 V…1000 kV
Main VT Sec’y: 80…140 V
CB1 CS VT Prim’y: 100 V…1000 kV
CB1 CS VT Sec’y: 80…140 V
CB2 CS VT Prim’y: 100 V…1000 kV
CB2 CS VT Sec’y: 80…140 V
Phase CT Primary: 1A…30 kA
Phase CT Sec’y: 1…5 A
SEF CT Primary: 1 A…30 kA
SEF CT Secondary: 1…5 A
MComp CT Primary: 1…30 k
MComp CT Sec’y: 1…5 A
CS Input: A-N, B-N, C-N,
A-B, B-C, C-A
CT1 Polarity: Standard/Inverted
CT2 Polarity: Standard/Inverted
SEF CT Polarity: Standard/Inverted
M CT Polarity: Standard/Inverted
VTs Connected: Yes/No
CB1 CS VT PhShft: -180…+180 deg
CB1 CS VT Mag.: 0.2…3
CB2 CS VT PhShft: -180…+180 deg
CB2 CS VT Mag.: 0.2…3
Sequence of event recorder (record
control)
Alarm Event: Disabled/Enabled
Relay O/P Event: Disabled/Enabled
Opto Input Event: Disabled/Enabled
General Event: Disabled/Enabled
Fault Rec Event: Disabled/Enabled
Maint Rec Event: Disabled/Enabled
Protection Event: Disabled/Enabled
Flt Rec Extended: Disabled/Enabled
DDB 31 - 0:
(up to):
DDB 1791 - 1760:
Binary function link strings, selecting which
DDB signals will be stored as events, and
which will be filtered out.
Oscillography (disturb recorder)
Duration: 0.10…10.50 s
Trigger Position: 0.0…100.0%
Trigger Mode: Single/Extended
Analog Channel 1:
(up to):
Analog Channel 12:
Disturbance channels selected from:
IA, IB, IC, IN, IN Sensitive, VA, VB, VC, IM,
V CheckSync (only for P543 and P545) and
IA2, IB2, IC2 and VCheckSync2 (only for P544
and P546)
Digital Input 1:
(up to):
Digital Input 32:
Selected binary channel assignment from
any DDB status point within the relay (opto
input, output contact, alarms, starts, trips,
controls, logic…).