Technical Data P54x/EN TD/La4
MiCOM P543, P544, P545 & P546
(TD) 2-13
TD
Input 1 Trigger: No Trigger/Trigger
(up to):
Input 32 Trigger: No Trigger/Trigger
Measured operating data
(measure't setup)
Default Display:
3Ph + N Current
3Ph Voltage
Power
Date and Time
Description
Plant Reference
Frequency
Access Level
Local Values: Primary/Secondary
Remote Values: Primary/Secondary
Measurement Ref: VA/VB/VC/IA/IB/IC
Measurement Mode: 0/1/2/3
Fix Dem Period: 1…99 mins
Roll Sub Period: 1…99 mins
Num Sub Periods: 1…15
Distance Unit: Miles/Kilometers
Fault Location:
Distance
Ohms
% of Line
Remote 2 Values: Primary/Secondary
Communications
RP1 Protocol:
Courier
IEC870-5-103
DNP3.0
IEC 61850
Courier protocol :
RP1 Address: 0…255
RP1 InactivTimer: 1…30 mins
RP1 PhysicalLink:
Copper
Fiber Optic
RP1 Port Config:
K Bus
EIA485 (RS485)
RP1 Comms Mode:
IEC 60870 FT1.2 Frame
IEC 60870 10-Bit Frame
RP1 Baud Rate:
9600 bits/s
19200 bits/s
38400 bits/s
IEC870-5-103 protocol :
RP1 Address: 0…255
RP1 InactivTimer: 1…30 mins
RP1 Baud Rate:
9600 bits/s
19200 bits/s
RP1 Meas Period: 1…60 s
RP1 PhysicalLink:
Copper
Fiber Optic
RP1 CS103 Blocking:
Disabled
Monitor Blocking
Command Blocking
DNP3.0 protocol : (EIA485)
RP1 Address: 0…65519
RP1 Baud Rate:
1200 bits/s
2400 bits/s
4800 bits/s
9600 bits/s
19200 bits/s
38400 bits/s
RP1 Parity: Odd/Even/None
RP1 PhysicalLink: Copper
Fiber Optic
RP1 Time Sync: Disabled/Enabled
Meas Scaling: Primary, Secondary or
Normalized.
Message gap: 0…50 ms
DNP Need time: 1...30 mins
DNP App Fragment: 100...2048
DNP App Timeout: 1...120 s
DNP SBO Timeout: 1...10 s
DNP Link Timeout: 0.1...60 s
DNP3.0 protocol : (Ethernet)
DNP Time Sync: Disabled/Enabled
Meas Scaling: Primary, Secondary or
Normalized.
NIC Tunl Timeout: 1...30 mins
NIC Link Report: Alarm, Event, None
NIC Link Timeout: 0.1...60 s
DNP Need time: 1...30 mins
DNP App Fragment: 100...2048
DNP App Timeout: 1...120 s
DNP SBO Timeout: 1...10 s
DNP Link Timeout: 0.1...60 s
IEC61850 protocol : (Ethernet)
NIC Tunl Timeout: 1...30mins
NIC Link Report: Alarm, Event, None
NIC Link Timeout: 0.1...60s
Optional additional second rear
communication (rear port2 (RP2))
RP2 Protocol: Courier (fixed)
RP2 Port Config:
Courier over EIA(RS)232
Courier over EIA(RS)485
K-Bus
RP2 Comms. Mode:
IEC60870 FT1.2 Frame
10-Bit NoParity
RP2 Address: 0…255
RP2 InactivTimer: 1…30 mins
RP2 Baud Rate:
9600 bits/s
19200 bits/s
38400 bits/s