P54x/EN TD/La4 Technical Data
(TD) 2-14
MiCOM P543, P544, P545 & P546
TD
Commission tests
Monitor Bit 1:
(up to):
Monitor Bit 8:
Binary function link strings, selecting which
DDB signals have their status visible in the
Commissioning menu, for test purposes
Test Mode:
Disabled
Test Mode
Blocked Contacts
Test Pattern:
Configuration of which output contacts are to
be energized when the contact test is
applied.
Contact Test: No Operation,
Apply Test,
Remove Test
Test LEDs: No Operation
Apply Test
Test Auto-reclose: No Operation
Trip 3 Pole
Trip Pole A
Trip Pole B
Trip Pole C
Static Test Mode: Disabled/Enabled
Static Test: Disabled/Enabled
Loopback Mode: Disabled/Internal/External
IM64 TestPattern:
Configuration of which InterMiCOM
64
commands are to be set high or low for a
loopback test.
IM
64
Test Mode: Disabled/Enabled
Circuit breaker condition monitoring
(CB Monitor setup)
P543and P545 CB monitor setup :
Broken I^: 1.0…2.0
I^ Maintenance: Alarm
Disabled/Enabled
I^ Maintenance: 1…25000
I^ Lockout: Alarm Disabled/Enabled
I^ Lockout: 1…25000
No. CB Ops Maint: Alarm
Disabled/Enabled
No. CB Ops Maint: 1…10000
No. CB Ops Lock: Alarm
Disabled/Enabled
No. CB Ops Lock: 1…10000
CB Time Maint: Alarm
Disabled/Enabled
CB Time Maint: 0.005…0.500s
CB Time Lockout: Alarm
Disabled/Enabled
CB Time Lockout: 0.005…0.500s
Fault Freq. Lock: Alarm
Disabled/Enabled
Fault Freq. Count: 1…9999
Fault Freq. Time: 0…9999s
P544 and P546 CB monitor setup :
CB1 Broken ^: 1…2
CB1 ^ Maintenance: Alarm Disabled/
Alarm Enabled
CB1 ^ Maintenance: 1…25000 n^
CB1 ^ Lockout: Alarm Disabled/
Alarm Enabled
CB1 ^ Lockout: 1…25000 n^
No. CB1 Ops. Maint.: Alarm Disabled/
Alarm Enabled
No. CB1 Ops. Maint.: 1…10000
No. CB1 Ops. Lock: Alarm Disabled/
Alarm Enabled
No. CB1 Ops. Lock: 1…10000
CB1 Time Maint.: Alarm Disabled/
Alarm Enabled
CB1 Time Maint.: 0.005…0.5 s
CB1 Time Lockout: Alarm Disabled/
Alarm Enabled
CB1 Time Lockout: 0.005…0.5 s
CB1 Fault Freq. Lock: Alarm Disabled/
Alarm Enabled
CB1 Flt Freq. Count: 1…9999
CB1 Flt Freq. Time: 0…9999 s
CB2 Broken ^:
(up to)
CB2 Flt Freq. Time:
All settings selected from the same ranges
as per the first controlled circuit breaker,
CB1.
Optocoupled binary inputs
(opto config.)
Global threshold:
24 - 27 V
30 - 34 V
48 - 54 V
110 - 125 V
220 - 250 V
Custom
Opto Input 1:
(up to):
Opto Input #. (# = max. opto no. fitted):
Custom options allow independent
thresholds to be set per opto, from the same
range as above.
Filter Control:
Binary function link string, selecting which
optos will have an extra 1/2 cycle noise filter,
and which will not.
Characteristics:
Standard 60% - 80%
50% - 70%
Control inputs into PSL
(ctrl. I/P config.)
Hotkey Enabled:
Binary function link string, selecting which of
the control inputs will be driven from
Hotkeys.
Control Input 1: Latched/Pulsed
(up to):

Table of Contents