Technical Data P54x/EN TD/La4
MiCOM P543, P544, P545 & P546
(TD) 2-15
TD
Control Input 32: Latched/Pulsed
Ctrl Command 1:
(up to):
Ctrl Command 32:
ON/OFF
SET/RESET
IN/OUT
ENABLED/DISABLED
Function keys
Fn. Key Status 1:
(up to):
Fn. Key Status 10
Disable
Lock
Unlock/Enable
Fn. Key 1 Mode: Toggled/Normal
(up to):
Fn. Key 10 Mode: Toggled/Normal
Fn. Key 1 Label:
(up to):
Fn. Key 10 Label:
User defined text string to describe the
function of the particular function key
IED configurator
Switch Conf. Bank: No Action/Switch Banks
IEC 61850 GOOSE
GoEna: Disabled/Enabled
Test Mode: Disabled/Pass Through/Forced
VOP Test Pattern: 0x00000000...
0xFFFFFFFF
Ignore Test Flag: No/Yes
Prot comms/IM
64
Scheme Setup:2 Terminal/Dual Redundant/3
Terminal
Address: 0-0, 1-A…20-A, 1-B….20-B
Address: 0-0, 1-A…20-A, 1-B….20-B,
1-C…20-C
Comm Mode: Standard/IEEE C37.94
Baud Rate Ch 1: 56kbits/s or 64kbits/s
Baud Rate Ch 2: 56kbits/s or 64kbits/s
Clock Source Ch1: Internal/External
Clock Source Ch2: Internal/External
Ch1 N*64kbits/s: Auto, 1, 2, 3... 12
Ch2 N*64kbits/s: Auto, 1, 2, 3... 12
Comm Delay Tol: 0.001 s...0.00005 s
Comm Fail Timer: 0.1 s...600 s
Comm Fail Mode: Ch 1 Failure/Ch 2 Failure/
Ch 1 or Ch 2 Fail/Ch 1 and Ch 2 Fail
GPS Sync: Enabled or Disabled
Char Mod Time: 0...2 s
Prop Delay Equal: No operation/Restore CDiff
Re-Configuration: Three Ended/Two Ended
(R1&R2)/Two Ended (L&R2)/Two Ended
(L&R1)
Channel Timeout: 0.1 s...10 s
Alarm Level: 0%...100%
Prop Delay Stats: Disabled/Enabled
MaxCh 1 PropDelay: 1 m...50 ms
MaxCh 2 PropDelay: 1 m...50 ms
TxRx Delay Stats: Disabled/Enabled
MaxCh1 Tx-RxTime: 1 m...50 ms
MaxCh2 Tx-RxTime: 1 m...50 ms
GPS Fail Timer: 0…9999 s
GPS Trans Fail: Disabled/Enabled
GPS Trans Count: 1…100 s
GPS Trans Timer: 0…9999 s
IM1 Cmd Type: Direct/Permissive
IM1 FallBackMode: Default/Latching
IMx(x=1 to 8) DefaultValue: 0 or 1
The IM1 – IM8 s setting are common to both
Ch1 and Ch2 (i.e. if IM1 DefaultValue is set
to 0, it will be 0 on Ch1 and on Ch2)
Control input user labels
(Ctrl. I/P labels)
Control Input 1:
(up to):
Control Input 32:
User defined text string to describe the
function of the particular control input
Settings in multiple groups
Note: All settings here onwards apply for
setting groups # = 1 to 4.
Protection functions
Line parameters
GROUP # (for # = 1 to 4)
Line Length (km): 0.30…1000.00 km
Line Length (miles): 0.20…625.00 mi
Line Impedance: 0.05…500.00/In
Line Angle: 20…90°
Residual Comp: 0.00…10.00
Residual Angle: -180…90°
Mutual Comp: Disabled/Enabled
KZm Mutual Set: 0.00…10.00
KZm Mutual Angle: -180…90°
Mutual cut-off (k): 0.0…2.0
Phase Sequence:
Standard ABC
Reverse ACB
CB Tripping Mode (per CB as appropriate):
3 Pole
1 and 3 Pole
Line Charging Y: 0.00…10.00 ms
Distance setup
Setting Mode: Simple/Advanced