P54x/EN TD/La4 Technical Data
(TD) 2-16
MiCOM P543, P544, P545 & P546
TD
Phase distance
Phase Chars.: Mho/Quadrilateral Quad
Resistance: Common/Proportional
Fault Resistance: 0.05…500.00/In
Zone 1 Ph Status: Disabled/Enabled
Zone 1 Ph Reach: 10…1000% of line
Zone 2 Ph Status: Disabled/Enabled
Zone 2 Ph Reach: 10…1000% of line
Zone 3 Ph Status: Disabled/Enabled
Zone 3 Ph Reach: 10…1000% of line
Zone 3 Ph Offset: Disabled/Enabled
Z3Ph Rev Reach: 10…1000% of line
Zone P Ph Status: Disabled/Enabled
Zone P Ph Dir.: Forward/Reverse
Zone P Ph Reach: 10…1000% of line
Zone 4 Ph Status: Disabled/Enabled
Zone 4 Ph Reach: 10…1000% of line
Ground distance
Ground Chars.: Mho/Quadrilateral
Quad Resistance: Common/Proportional
Fault Resistance: 0.05…500.00/In
Zone1 Gnd Status: Disabled/Enabled
Zone1 Gnd Reach: 10…1000% of line
Zone2 Gnd Status: Disabled/Enabled
Zone2 Gnd Reach: 10…1000% of line
Zone3 Gnd Status: Disabled/Enabled
Zone3 Gnd Reach: 10…1000% of line
Zone3 Gnd Offset: Disabled/Enabled
Z3Gnd Rev Reach: 10…1000% of line
ZoneP Gnd Status: Disabled/Enabled
ZoneP Gnd Direction: Forward/Reverse
ZoneP Gnd Reach: 10…1000% of line
Zone4 Gnd Status: Disabled/Enabled
Zone4 Gnd Reach: 10…1000% of line
Digital Filter:
Standard
Special Applics
CVT Filters:
Disabled
Passive
Active
SIR Setting: (for CVT): 5…60
Load Blinders: Disabled/Enabled
Load/B Impedance:
0.10…500.00/In
Load/B Angle: 15…65°
Load Blinder V<: 1.0…70.0 V (ph-g)
Distance Polarizing: 0.2…5.0
Delta Status: Disabled/Enabled
Delta Char Angle: 0°...90°
Delta V Fwd: 1.0…30.0 V
Delta V Rev: 0.5…30.0 V
Delta I Fwd: 0.10…10.00 In
Delta I Rev: 0.05…10.00 In
Distance elements - phase distance
Z1 Ph. Reach: 0.05…500.00/In
Z1 Ph. Angle: 20…90°
R1 Ph. Resistive: 0.05…500.00/In
Z1 Tilt Top Line: -30…30°
Z1 Ph. Sensit. Iph>1: 0.050…2.000 In
Z2 Ph. Reach: 0.05…500.00/In
Z2 Ph. Angle: 20…90°
Z2 Ph Resistive: 0.05…500.00/In
Z2 Tilt Top Line: -30…30°
Z2 Ph. Sensit. Iph>2: 0.050…2.000 In
Z3 Ph. Reach: 0.05…500.00/In
Z3 Ph. Angle: 20…90°
Z3' Ph Rev Reach: 0.05…500.00/In
R3 Ph Res. Fwd.: 0.05…500.00/In
R3' Ph Res. Rev.: 0.05…500.00/In
Z3 Tilt Top Line: -30…30°
Z3 Ph. Sensit. Iph>3: 0.050…2.000 In
ZP Ph. Reach: 0.05…500.00/In
ZP Ph. Angle: 20…90°
ZP Ph Resistive: 0.05…500.00/In
ZP Tilt Top line: -30…30°
ZP Ph. Sensit. Iph>P: 0.050…2.000In
Z4 Ph. Reach: 0.05…500.00/In
Z4 Ph. Angle: 20…90°
Z4 Ph Resistive: 0.05…500.00/In
Z4 Tilt Top line: -30…30°
Z4 Ph. Sensit. Iph>4: 0.050…2.000 In
Ground distance parameters
Z1 Gnd. Reach: 0.05…500.00/In
Z1 Gnd. Angle: 20…90°
Z1 Dynamic Tilt: Disabled or Enabled
Z1 Tilt top line: -30°...30°
kZN1 Res. Comp.: 0.00…10.00
kZN1 Res. Angle: -180…90°
kZm1 Mut. Comp.: 0.00…10.00
kZm1 Mut. Angle: -180…90°
R1 Gnd. Resistive: 0.05…500.00/In
Z1 Sensit Ignd>1: 0.050…2.000 In
Z2 Gnd. Reach: 0.05…500.00/In
Z2 Gnd. Angle: 20…90°
Z2 Dynamic Tilt: Disabled or Enabled
Z2 Tilt top line: -30°...30°
kZN2 Res. Comp.: 0.00…10.00
kZN2 Res. Angle: -180…90°
kZm2 Mut. Comp: 0.00…10.00
kZm2 Mut. Angle: -180…90°
R2 Gnd Resistive: 0.05…500.00/In
Z2 Sensit Ignd>2: 0.050…2.000 In
Z3 Gnd. Reach: 0.05…500.00/In
Z3 Gnd. Angle: 20…90°
Z3 Dynamic Tilt: Disabled or Enabled
Z3 Tilt top line: -30°...30°
Z3' Gnd Rev Rch: 0.05…500.00/In
kZN3 Res. Comp.: 0.00…10.00
kZN3 Res. Angle: -180…90°
kZm3 Mut. Comp.: 0.00…10.00
kZm3 Mut. Angle: -180…90°
R3 Gnd Res. Fwd: 0.05…500.00/In
R3 Gnd Res. Rev: 0.05…500.00/In
Z3 Sensit Ignd>3: 0.050…2.000 In
ZP Ground Reach: 0.05…500.00/In
ZP Ground Angle: 20…90°
ZP Dynamic Tilt: Disabled or Enabled
ZP Tilt top line: -30°...30°
kZNP Res. Comp.: 0.00…10.00