RPV311
Chapter 4 Configuration
RPV311-TM-EN-6
113
Channel name
RA33x input
Channel type
DNP3 Database associated number
D1
A201
Physical
00
D2
A217
Physical
01
D4
C201
Physical
02
D_Linha2
B201
Physical
03
D_Linha3
B202
Physical
04
G1
GOOSE
G2
GOOSE
D10
A210
Physical
05
D11
A211
Physical
06
D12
A212
Physical
07
18.2.2 ADDING ANALOG CHANNELS
The analog data possibilites for the DNP3 communication procol are the same as for MODBUS. The
MODBUS analog data are shown in section 2.3.
To configure the analog data, access the MODBUS/DNP3 menu via web interface. Analog data are added in a
sequential way, like the digital channels, but the starting number for the analog channels is 5. Numbers 0, 1,
2, 3 and 4 are reserved for equipment information.
Note:
For analog channels, the first number associated at the DNP3 database is 5. Numbers 1, 2, 3
and 4 are reserved for equipment information.
Figure 44 shows the analog channels selected at the MODBUS/DNP3 menu and the table below it shows the
associated number at the DNP3 database for each example analog channel.