EasyManua.ls Logo

Alstom Reason RPV311 - Accuracy Limits

Alstom Reason RPV311
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 8 PMU
RPV311
186
RPV311-TM-EN-6
2.2 ACCURACY LIMITS
The Total Vector Error defined through

󰇛
󰇛󰇜
󰇜
󰇛
󰇛󰇜
󰇜
Represents the magnitude of the error vector, obtained by subtracting the measured synchrophasor of the
theoretical value. It is represented as a fraction of the magnitude of the theoretical value.
In the equation above,
󰇛󰇜 and
󰇛󰇜 are the measured values, while
and
are the theoretical values
of the input signal at the instant of measurement.
Considering acquisition modules appropriate for PMU measurement, the unit is rated as level 1 compliant
according to IEEE C37.118 under the condition below.
Influence quantity
Range
TVE max
Signal frequency
± 5 Hz of
Fnom
1 %
Signal magnitude
10 % … 120 %
rated
1 %
Phase angle
± 180 %
1 %
Harmonic distortion
10 % ¹
1 %
Out-of-band interfering signal ³
10 % ²
1 %
¹ Any harmonic up to 50

order
² Of input signal magnitude
³
frequency of interfering signal,
nominal frequency and
synchrophasors broadcast frequency
2.3 COMMUNICATION PORTS, TRANSMISSION RATES
Each stream of data is transmitted through a particular UDP/IP port listed in the table below:

Table of Contents