RPV311
Chapter 8 PMU
RPV311-TM-EN-6
187
Stream of data
Port number
1
4713
2
4714
3
4715
4
4716
The transmission rate options at 60Hz are: 10, 12, 15, 20, 30, or 60 frames per second At 50Hz the rates
are: 10, 25, or 50 frames per second.
2.4 TIMESTAMP
The reported timestamp is synchronized to the UTC second rollover and refers to the middle of the sampling
window.
2.5 CONFIGURATION
The PMU configuration is carried out through the Web Interface. For details about the PMU configuration,
see Chapter 4.
2.6 STANDARDS COMPLIANCE
The RPV311 PMU complies with the following standards:
IEEE C37.118-2005
IEEE C37.118.1-2011
IEEE C37.118.2-2011
IEEE C37.118.1a-2014